ruby panel range ruby panel range

Basic condensing unit & scroll starter panels



A compact starter control panel to fit into any housing or small space.


Contactor with overload protection & anti short cycling timer.


Terminals for HP switch, Crankcase Heater, Oil Separator heater, fan speed controller & single phase condenser fan motor.


310mm H x 130mm W x 130mm D


OVERLOAD SIZE MODEL CONTACTOR SIZE ISOLATOR SIZE CABLE SIZE
4.0-6.5A RUS 1 16A 16A 2.5MM
6.0-8.5A RUS 2 16A 16A 2.5MM
7.5-11A RUS 3 16A 16A 2.5MM
10-14A RUS 4 16A 16A 2.5MM
13-19A RUS 5 25A 25A 4MM
18-25A RUS 6 25A 45A 4MM
24-32A RUS 7 30A 45A 6MM


ruby panel range

Ruby Plus Range


A more robust starter panel in a mild steel enclosure with a hinged door & function indicators.



Direct on line Options


OVERLOAD SIZE MODEL CONTACTOR SIZE ISOLATOR SIZE CABLE SIZE
4.0-6.5A RUMS 1 16A 16A 2.5MM
6.0-8.5A RUMS 2 16A 16A 2.5MM
7.5-11A RUMS 3 16A 16A 2.5MM
10-14A* RUMS 4 16A 16A 2.5MM
13-19A* RUMS 5 25A 25A 4MM
18-25A* RUMS 6 25A 45A 4MM
24-32A* RUMS 7 30A 45A 6MM


Size 500mm H x 300mm W x 150mm D



Part wind start options


MOTOR SIZE MODEL CONTACTOR SIZE ISOLATOR SIZE CABLE SIZE
5HP RU PWS 1 2 x 16A 40A 2.5MM
7.5HP RU PWS 2 2 x 16A 40A 2.5MM
10HP RU PWS 3 2 x 16A 40A 4MM
15HP RU PWS 4 2 x 26A 40A 6MM
20HP RU PWS 5 2 x 30A 80A 10MM
25HP RU PWS 6 2 x 30A 80A 10MM
30HP RU PWS 7 2 x 40A 80A 16MM


Sizes start at 500mm H x 400mm W x 150mm D



Star Delta start options


MOTOR SIZE MODEL CONTACTOR SIZE ISOLATOR SIZE CABLE SIZE
5HP RU SDS 1 3 x 16A 40A 2.5MM
7.5HP RU SDS 2 3 x 16A 40A 2.5MM
10HP RU SDS 3 3 x 16A 40A 4MM
15HP RU SDS 4 2 x 26A 1 x 16A 40A 6MM
20HP RU SDS 5 2 x 30A 1 x 26A 80A 10MM
25HP RU SDS 6 2 x 30A 1 x 26A 80A 10MM
30HP RU SDS 7 2 x 40A 1 x 30A 80A 16MM


Sizes start at 500mm H x 400mm W x 150mm D